ELECTRIC MOTORS, GEARMOTORS AND DRIVESVariable Speed AC Motor DrivesSM-BasicInstallation and Operation Manual
66.1 INSTALLATION AFTER A LONG PERIOD OF STORAGEIf input power has not been applied to the drive for a period of time exceeding three years (due tosto
7WARNING!Hazard of electrical shock! Capacitors retain charge after power is removed. Disconnect incomingpower and wait until the voltage between te
8Minimum voltage rating of the protection device should be 250 Vac for 120/208/240 Vac and 208/240 Vac rated drives.UL Class CC fast-acting, current l
9THREE PHASE INPUT(where applicable)3 PHASEAC MOTOR120 Vac SINGLE PHASE INPUT(where applicable)208/240 Vac SINGLE PHASE INPUT(where applicable)DC BUSV
1010.0 CONTROL WIRING10.1 CONTROL WIRING VS. POWER WIRINGExternal control wiring MUST be run in a separate conduit away from all other input and outpu
1110.5 SPEED REFERENCE SELECTIONIf a speed pot is to be used to control the drive speed, terminal TB-13A, 13B, or 13C (Parameter 10,11, or 12) may be
1210.7 DRIVE STATUS DIGITAL OUTPUTSThere is one open-collector output at terminal TB-14. The open-collector circuit is a current-sinkingtype rated at
1311.0 SM-Basic CONTROL WIRING DIAGRAMS11.1 TWO-WIRE START/STOP CONTROLNOTES:1. Close TB-1 to TB-11 to RUN, and open to STOP. TB-1 functions as a RUN
1411.2 THREE-WIRE START/STOP CONTROLNOTES:1. Program TB-13C (Parameter 12) for START FORWARD (05).2. If reverse direction is required, set ROTATION (P
1511.3 PRESET SPEEDS (WITH TWO-WIRE START/STOP CONTROL)NOTES:1. For preset speed control, all or some of the TB-13 terminals must be programmed as pre
EC Declaration of ConformityIn accordance with EN45014:1998We,Leeson Electric Corporation2100 Washington StreetGrafton, Wisconsin 53024USAdeclare unde
1612.0 INITIAL POWER UP AND MOTOR ROTATIONIf input power has not been applied to the drive for a period of time exceeding three years (due tostorage,
17Follow the procedure below to check the motor rotation. This procedure assumes that the drive hasbeen powered up for the first time, and that none
18Press Mode to enter passwordUse s and t to scroll to thepassword value13.0 PROGRAMMING THE SM-Basic DRIVEThe drive may be programmed by one of two m
19NOTE: If the display flashes “Er”, the password was incorrect, and the process to enter the passwordmust be repeated.Use the s and t buttons to scr
2013.2 ELECTRONIC PROGRAMMING MODULE (EPM)Every SM-Basic Series drive has an Electronic Programming Module (EPM) installed on themain control board.
2114.0 PARAMETER MENUNOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.FACTORYFACTORYFACTORYFA
22NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.NOTE 2: If LINE VOLTAGE is set to LOW, max
23NOTE: If this parameter is changed while the drive is running, the new value will not take effectuntil the drive is stopped.02 CARRIER FREQUENCYThi
2403 START METHOD01 NORMAL: The drive will start when the appropriate contact is closed on the terminal strip.See Section 11 for possible control con
2504 STOP METHOD01 COAST TO STOP: When a STOP command is given, the drive shuts off the output to themotor, allowing it to coast freely to a stop.02
Manual Number: IMSN01TABLE OF CONTENTS1.0 GENERAL... 1 2.0 SM-Bas
2606 AT SET SPEED: Closes if the drive is within + 0.5 Hz of the speed setpoint.07 ABOVE PRESET SPEED #3: Closes if the output frequency exceeds PRE
2708 DB FAULT: Sets TB-13A as a dynamic braking fault input when used with the optional dynamicbraking module. When this input is activated by the d
2808 DB FAULT: Used with the optional dynamic braking module. When this input is activated bythe dynamic braking module, the drive will trip into a
2909 ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into ACCEL/DECEL #2 (Parameter 42).NOTE: If the optional remote keypa
3019 ACCELERATION TIMEThis sets the acceleration rate for all of the speed reference sources (keypad, speed pot, jog, MOP,and preset speeds). This se
31When using a speed pot reference, this parameter also sets the drive speed that corresponds to themaximum analog input (10 VDC).NOTE: If this param
322 8 FIXED BOOSTFIXED BOOST increases starting torque by increasing the output voltage when operating below halfof the base frequency, which increase
33NOTE 2: When a TB-13 terminal is programmed for a function other than a preset speed select, it isconsidered OPEN for the table above.Preset Speed
344 8 PROGRAM SELECTIONThis is used to select whether the drive will operate according to the user settings or the optionalOEM default settings, and t
355 0 FAULT HISTORYThe FAULT HISTORY stores the last eight faults that tripped the drive. Refer to Section 16.0 -TROUBLESHOOTING for a list of the fa
INPUT POWER TERMINALSOUTPUT (MOTOR) TERMINALSCONTROLTERMINALSTRIP2-DIGIT LEDDISPLAYELECTRONICPROGRAMMINGMODULE (EPM)PROGRAMMINGBUTTONSTHE SM-Basic
36NOTE: FCLIM is an abbreviation for Fast Current Limit.FCLIMModeOUTPUTFAULTst58 KEYPAD AND PROTECTION STATUSThis indicate the status of the buttons
37Press Mode to view parameter contents(77 = 77% LOAD)Press Mode again to exitUpper right decimal point blinksPress Mode onceUpper right decimal point
38The table below lists the fault conditions that will cause the drive to shut down, as well as somepossible causes. Please contact the factory for m
3917.0 SM-Basic DISPLAY MESSAGESThe following describes the various displays and messages that can appear on the SCN drive.17.1 SPEED DISPLAYIf the dr
40NOTE: The speed source displays will flash when the speed reference source is changed while thedrive is running to indicate that the new speed refe
4118.0 USER SETTING RECORDNO.NO.NO.NO. PARAMETER NAMEPARAMETER NAMEPARAMETER NAMEPARAMETER NAME FACTORY DEFAULTFACTORY DEFAULTFACTORY DEFAULTFACTORY D
42NO.NO.NO.NO. PARAMETER NAMEPARAMETER NAMEPARAMETER NAMEPARAMETER NAME FACTORY DEFAULTFACTORY DEFAULTFACTORY DEFAULTFACTORY DEFAULT USER SETTINGUSER
Service Dept. FAX (262)-377-00904/00
11.0 GENERAL1.1 PRODUCTS COVERED IN THIS MANUALThis manual covers the Leeson Electric Corporation SM-Basic SeriesVariable Frequency Drive.1.2 PRODUCT
22.0 SM-Basic DIMENSIONSMounting Tab DetailDHWRP0.38"0.38"0.18"0.69" 0.19"Dia. Slot208/240 174387 5.75 2.88 5.56 2.60 4.
33.0 SM-Basic MODEL DESIGNATION CODE4.0 SM-Basic SPECIFICATIONS1WARNING: Control terminals are not isolated from line voltage! Do not touch!Storage T
45.0 SM-Basic RATINGSWATTS(NOTE 3)WATTS(NOTE 3)INPUT OUTPUTMODELNUMBERFOR MOTORSRATEDINPUTPHASECURRENT(AMPS)(NOTE 1)POWER(kVA)CURRENT(AMPS)(NOTE 1)174
56.0 INSTALLATIONSM-Basic models are suitable for UL pollution degree 2 environment only, and MUST beinstalled in an electrical enclosure which will p