SUB-MICRO SERIES DYNAMIC BRAKING OPTION (FOR MODELS RATED 0.25 - 10 HP)
INSTALLATION AND OPERATION INSTRUCTIONS
Manual Number: SDBR06C
The Sub-Micro Series Dynamic Braking option can be used with all SM, SM-Plus and SM-Basic models.
WARNING!
Remove power from the drive and wait three minutes before wiring the DB module. Incorrect wiring of the B+ and B- terminals will result in
equipment damage! The B+ terminal on the DB module must be connected to the B+ terminal on the Sub Micro drive, and the B- terminal on the DB
module must be connected to the B- terminal on the Sub-Micro drive.
DO NOT make connections to R+ and R- without consulting LEESON. Damage to the Dynamic Braking module and/or drive may result.
!
SM-PLUS SERIES DRIVES
PROGRAMMING
1. Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).
2. Set Parameter 10 (TB-13A FUNCTION) to DB FAULT (09), or set Parameter 12
(TB-13C FUNCTION) to DB FAULT (08).
WIRING
The diagram to the right illustrates how the DB module is wired to the SM-PLUS Series
drive. In this diagram, TB-13A is used as the DB FAULT input, but TB-13C could be
used instead if TB-13A is required for another function.
NOTE 1: Use 18 AWG wire for control connections.
NOTE 2: Use minimum 14 AWG wire for connections to B+ and B-. The B+ and B-
wires MUST be twisted together and must be less than 12 inches long.
NOTE 3: DO NOT make connections to R+ and R- without consulting LEESON.
Damage to the Dynamic Braking module and/or drive may result.
SM-PLUS
POWER
TERMINALS
SM-PLUS
CONTROL
TERMINALS
42
46
47
43
DB OPTION MODULE
13A231
GND
B - B + R + R -
B - B +
SM-PLUS DIAGRAM
(SEE NOTE 3)
SM SERIES DRIVES
PROGRAMMING
1. Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).
2. Set Parameter 10 (TB-13A FUNCTION) to INVERSE EXT. FAULT (09), or set
Parameter 11 (TB-13B FUNCTION) to INVERSE EXT. FAULT (10).
WIRING
The diagram to the right illustrates how the DB module is wired to the SM Series drive.
In this diagram, TB-13A is programmed for INVERSE EXTERNAL FAULT, but TB-
13B could be used instead if TB-13A is required for another function.
NOTE 1: Use 18 AWG wire for control connections.
NOTE 2: Use minimum 14 AWG wire for connections to B+ and B-. The B+ and B-
wires MUST be twisted together and must be less than 12 inches long.
NOTE 3: DO NOT make connections to R+ and R- without consulting LEESON.
Damage to the Dynamic Braking module and/or drive may result.
SM
POWER
TERMINALS
SM
CONTROL
TERMINALS
42
46
47
43
DB OPTION MODULE
13A13E 11
GND
B - B + R + R -
B - B +
SM DIAGRAM
(SEE NOTE 3)
2
LEESON ElectricLEESON Electric
LEESON ElectricLEESON Electric
LEESON Electric • 2100 Washington St. • Grafton, WI 53024 • Ph: (262) 377-8810 • Fax: (262) 377-9025 • www.leeson.com
Przeglądanie stron 0
1 2

Podsumowanie treści

Strona 1 - SM SERIES DRIVES

SUB-MICRO SERIES DYNAMIC BRAKING OPTION (FOR MODELS RATED 0.25 - 10 HP)INSTALLATION AND OPERATION INSTRUCTIONSManual Number: SDBR06CThe Sub-Micro Seri

Strona 2 - SM-BASIC SERIES DRIVES

MOUNTING THE DYNAMIC BRAKING MODULEThe diagram below illustrates how to mount the DB Module. The DBModule is compatible with the DIN Rail Mounting Ki

Komentarze do niniejszej Instrukcji

Brak uwag