Leeson SM-Plus Series Sub-Micro Inverters Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Oprogramowanie Leeson SM-Plus Series Sub-Micro Inverters. LEESON SM-Plus Series Sub-Micro Inverters User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - SPEEDMASTER

Installation and Operation ManualSPEEDMASTER®SM PLUS™ SERIES SUB-MICRO INVERTERS

Strona 2

6MODEL FOR MOTORS INPUT (50-60 Hz) OUTPUT HEAT LOSSNUMBER RATED INPUT CURRENT POWER CURRENT (WATTS)HP kW PHASE (AMPS) (NOTE 1) (kVA) (AMPS) (NOTE 2)12

Strona 3 - IMPORTANT NOTICE

7MODEL FOR MOTORS INPUT (50-60 Hz) OUTPUT HEAT LOSSNUMBER RATED INPUT CURRENT POWER CURRENT (WATTS)HP kW PHASE (AMPS) (kVA) (AMPS) (NOTE 2)400/480 Vac

Strona 4 - LEESON Electric

6.0 INSTALLATIONNOTE: SM-Plus™drives are intended for inclusion within other equipment, by professional electricalinstallers. They are not intended fo

Strona 5 - 1.0 GENERAL

96.2 EXPLOSION PROOF APPLICATIONSExplosion proof motors that are not rated for inverter use lose their certification when used for variablespeed. Due

Strona 6

107.1 INPUT VOLTAGE RATINGSDrives are rated for 120/208/240 Vac, single phase, 50-60 Hz input. The drive will function with inputvoltage of 120 Vac (+

Strona 7 - DIMENSIONS

7.2 INPUT FUSING AND DISCONNECT REQUIREMENTSA circuit breaker or a disconnect switch with fuses must be provided in accordance with the NationalElectr

Strona 8

8.0 POWER WIRINGHazard of electrical shock! Capacitors retain charge after power is removed. Disconnectincoming power and wait until the voltage betwe

Strona 9 - SPECIFICATIONS

13Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result.NOTES:1. WIRE AND GROUND IN ACCORDANCE WI

Strona 10 - 5.0 SM-Plus

1410.0 CONTROL WIRING10.1 CONTROL WIRING VS. POWER WIRINGExternal control wiring MUST be run in a separate conduit away from all other input and outpu

Strona 11

1510.6 SPEED REFERENCE SELECTIONIf an analog speed reference input is used to control the drive speed, terminal TB-13A, 13B, or 13C (Parameter 10, 11,

Strona 12 - 6.0 INSTALLATION

TABLE OF CONTENTS1.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12.0 SM-Plus™DIMENSIONS . . . . .

Strona 13

16NOTE: If TB-13A, TB-13B, and TB-13C are all programmed to select speed references, and two or threeof the terminals are closed to TB-2, the higher t

Strona 14

1711.0 SM-Plus™CONTROL WIRING DIAGRAMS11.1 SM-Plus™TERMINAL STRIPShown below is the terminal strip on the main control board, along with a brief descr

Strona 15

1811.2 TWO-WIRE START/STOP CONTROLShown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintainedcontact (suc

Strona 16 - 8.0 POWER WIRING

1911.3 ALTERNATE TWO-WIRE START/STOP CONTROLShown below is the wiring diagram for an alternate two-wire start/stop control scheme, using one maintaine

Strona 17 - POWER WIRING DIAGRAM

2011.4 THREE-WIRE START/STOP CONTROLShown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentarycontacts (suc

Strona 18 - 10.0 CONTROL WIRING

2111.5 SPEED POT AND PRESET SPEED CONTROLShown below is the wiring for SPEED POT and/or PRESET SPEED control, and either a two-wire orthree-wire start

Strona 19

2212.0 INITIAL POWER UP AND MOTOR ROTATIONDO NOT connect incoming AC power to output terminals T1, T2, and T3! Severedamage to the drive will result.

Strona 20 - TERMINAL STRIP

23Follow the procedure below to check the motor rotation. This procedure assumes that the drive has beenpowered up for the first time, and that none o

Strona 21 - CONTROL WIRING DIAGRAMS

2413.0 PROGRAMMING THE SM-Plus™DRIVEThe drive may be programmed by one of three methods: using the three buttons and 3-digit LED display on the front

Strona 22

25NOTE: If the display flashes “Er”, the password was incorrect, and the process to enter the password mustbe repeated.Use the ▲ and ▼ buttons to scro

Strona 23

IMPORTANT NOTICEThe following , and information is supplied to you for yourprotection and to provide you with m

Strona 24

13.1 SETTING VALUES IN TENTHS OF UNITS ABOVE 100Parameter settings and the keypad speed command can always be adjusted in tenths of unit incrementsfro

Strona 25

2713.2 ELECTRONIC PROGRAMMING MODULE (EPM)Every SM-Plus™drive has an Electronic Programming Module (EPM) installed on the main controlboard. The EPM s

Strona 26

2814.0 PARAMETER MENUFACTORYNO. PARAMETER NAME RANGE OF ADJUSTMENT DEFAULT(NOTE 1)01 LINE VOLTAGE HIGH (01), LOW (02) HIGH (01)02 CARRIER FREQUENCY 4

Strona 27

29FACTORYNO. PARAMETER NAME RANGE OF ADJUSTMENT DEFAULT(NOTE 1)12 TB-13C FUNCTION NONE (01), 0-10 VDC (02), 4-20mA (03), NONE (01)SELECT PRESET SPEED

Strona 28 - 13.0 PROGRAMMING THE SM-Plus

30FACTORYNO. PARAMETER NAME RANGE OF ADJUSTMENT DEFAULT(NOTE 1)27 BASE FREQUENCY 25.0 - 500.0 Hz (NOTE 4) 60.0 Hz28 FIXED BOOST 0.0 - 30.0 % 1.0 %29 A

Strona 29

3115.0 DESCRIPTION OF PARAMETERSP01 LINE VOLTAGE SELECTIONThis calibrates the drive for the actual applied input voltage, and can be set to HIGH (01)

Strona 30

NOTE 3: If this parameter is changed while the drive is running, the change will not take effect until the drive is stopped. Therefore, the allowable

Strona 31

33P04 STOP METHOD01 COAST TO STOP: When a STOP command is given, the drive shuts off the output to themotor, allowing it to coast freely to a stop.02

Strona 32 - 14.0 PARAMETER MENU

3406 AT SET SPEED: Closes if the drive is within ± 0.5 Hz of the speed setpoint.07 ABOVE PRESET SPEED #3: Closes if the output frequency exceeds the P

Strona 33

P10 TB-13A FUNCTION SELECTThis selects the function of terminal TB-13A. Closing TB-13A to TB-2 (or opening in the case ofsettings 7 and 10) activates

Strona 34

SUB-MICRO DRIVEINPUT POWERTERMINALSGROUND LUGELECTRONICPROGRAMMINGMODULE (EPM)PROGRAMMINGBUTTONSOUTPUT (MOTOR) TERMINALS3-DIGIT LEDDISPLAYCONTROLTERMI

Strona 35

01 NONE: Disables the TB-13B function.02 0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.03 4-20 mA: Selects a 4-20 mA

Strona 36

06 EXTERNAL FAULT: Sets TB-13C as a normally closed external fault input. If TB-13C is openwith respect to TB-2, the drive will fault.07 REMOTE KEYPAD

Strona 37

01 DISABLED: Disables the serial link02 9600, 8, N, 2- ENABLED WITH TIMER03 9600, 8, N, 2- ENABLED WITHOUT TIMER04 9600, 8, E, 1 - ENABLED WITH TIMER0

Strona 38

39P22 DC BRAKE VOLTAGEThis sets the magnitude of the DC braking voltage, in percentage of the nominal DC Bus voltage (DC Bus = input AC voltage X 1.41

Strona 39

40P26 MOTOR OVERLOADThe SM-Plus™is UL approved for solid state motor overload protection, and therefore does not requirea separate thermal overload re

Strona 40

P29 ACCELERATION BOOSTACCELERATION BOOST helps accelerate high-inertia loads. During acceleration, the output voltageis increased to increase motor to

Strona 41

42Example: The critical frequency is 23 Hz, and it is desired to skip a frequency range of 3 Hz above andbelow the critical frequency (therefore the s

Strona 42

43Example: A 0-10 VDC signal is required to indicate 0-150% load. Setting this parameter to 150% willyield 10 VDC at 150% load.P42 ACCEL / DECEL #2Thi

Strona 43

04 RESET 60: Resets the users parameters to the factory defaults for a 60 Hz base frequency.05 RESET 50: Resets the user parameters to the factory def

Strona 44

P52 DC BUS VOLTAGEThis displays the DC bus voltage in percent of nominal. Nominal DC bus voltage is determined bymultiplying the drive’s nameplate inp

Strona 45

1.0 GENERAL1.1 PRODUCTS COVERED IN THIS MANUALThis manual covers the LEESON Electric SM-Plus™Variable Frequency Drive.1.2 PRODUCT CHANGESLEESON Electr

Strona 46

P58 KEYPAD AND PROTECTION STATUSThis indicates the status of the buttons on the keypad, and the status of the protective circuitry in the drive, using

Strona 47

16.0 TROUBLESHOOTINGTo aid in troubleshooting, Parameters 50 through 60 can be accessed without entering the PASSWORD.Simply press the Mode button twi

Strona 48

The table below lists the fault conditions that will cause the drive to shut down, as well as some possiblecauses. Please contact the factory for more

Strona 49

17.0 SM-Plus™DISPLAY MESSAGESThe following describes the various displays and messages that can appear on the SM-Plus™drive.17.1 SPEED DISPLAYIf the d

Strona 50

50NOTE: The speed source displays will flash when the speed reference source is changed while the driveis running to indicate that the new speed refer

Strona 51 - 16.0 TROUBLESHOOTING

APPENDIX B – PI SETPOINT CONTROL OPTIONThe following describes the PI Setpoint Control software option for the SM-Plus™drive. This softwareoption has

Strona 52

B.3 SETPOINT REFERENCESThe following references can be used to adjust the process setpoint:1. Keypad (▲ and ▼ buttons)2. 0-10 VDC signal (from speed p

Strona 53 - DISPLAY MESSAGES

B.5 DESCRIPTION OF PI PARAMETERSP10 TB-13A FUNCTION SELECT12 KEYPAD SETPOINT: This option has been added so that the ▲ and ▼ buttons on the frontof th

Strona 54

P63 MAX FEEDBACKThis parameter should be set to the value of the process variable that corresponds to the maximum transducer feedback signal (10 VDC o

Strona 55 - B.2 FEEDBACK DEVICES

P69 0-10 VDC FEEDBACKThis can be used to monitor the PI feedback when using a 0-10 VDC feedback signal. The displayedvalue will be scaled according to

Strona 56 - B.3 SETPOINT REFERENCES

1.4 RECEIVINGInspect all cartons for damage which may have occurred during shipping. Carefully unpack equipmentand inspect thoroughly for damage or sh

Strona 57

P76 SLEEP DELAYThis sets the amount of time the drive must operate below the SLEEP THRESHOLD (see P75 on theprevious page) before the drive “goes to s

Strona 58

P45 SPEED AT MIN SIGNALThis sets the speed at which the drive will run when it receives the minimum speed reference signal (0VDC or 4 mA). This is use

Strona 59

• Open TB-13A to TB-2 to disable PI mode and control speed directly by the method selected inSTANDARD SPEED SOURCE (Parameter 05). For example, if Par

Strona 60

B.8 TUNING THE PI CONTROLOnce the PI control is configured properly, it needs to be tuned in order to maintain the process setpoint.First, set the Int

Strona 61 - PI CONTROL WIRING EXAMPLES

EC DECLARATION OF CONFORMITYIn accordance with EN45014:1998Applied Council Directive(s): EMC Directive 89/336/EEC, as amended: 92/31/EECand Low Voltag

Strona 64

3INPUTHP kW VOLTAGE MODEL H W D P R0.25 0.20 208 / 240 174452 5.75 (146) 2.88 (73) 3.94 (100) 0.80 (20) 4.37 (111)0.5 0.37 208 /240 174453 5.75 (146)

Strona 65

4INPUTHP kW VOLTAGE MODEL H W D P R2 1.5 208 / 240 174494 5.75 (146) 3.76 (96) 6.74 (171) 3.40 (86) 4.37 (111)208 / 240 174457 5.75 (146) 2.88 (73) 5.

Strona 66 - 4914S/7.5K/3-05/CP/BH

54.0 SM-Plus™SPECIFICATIONSStorage Temperature -20° to 70° CAmbient Operating Temperature 0° to 50° C (derate 2.5% per °C above 50°)Ambient Humidity &

Komentarze do niniejszej Instrukcji

Brak uwag